Information
What Is an RCBO? RCBO Meaning, Types and RCBO vs MCB Explained
Updated October 2026 · Meteor Electrical guides · 9 min read
Quick answer: An RCBO (residual current breaker with overcurrent protection) is one device that combines an MCB and an RCD. It switches off a single circuit if it detects an overload, a short circuit or earth leakage, usually at 30 mA. That protects the cable and the people using it, and a fault only cuts the power to that one circuit.

RCBOs are now the standard choice for new consumer units in UK and Irish homes. This guide explains what RCBO means, how it differs from an MCB and an RCD, what the B, C, A, F and AC markings mean, and how to choose the right one.
In this guide
- What is an RCBO and what does RCBO stand for?
- How does an RCBO work?
- RCBO vs MCB vs RCD: what is the difference?
- What are the different RCBO types?
- What does 30mA mean on an RCBO?
- Single-module vs 2-module RCBOs: which do you need?
- Why are RCBO consumer units so popular?
- How do you choose and test an RCBO?
- FAQs
What is an RCBO and what does RCBO stand for?
RCBO stands for residual current breaker with overcurrent protection. Its full name in the product standard, BS EN 61009, is a residual current operated circuit-breaker with integral overcurrent protection. In plain terms, it is an MCB and an RCD built into one device.
- The MCB part protects the circuit cable against overload and short circuit.
- The RCD part detects current leaking to earth, which could be flowing through a person, and disconnects fast enough to reduce the risk of a serious electric shock.
Because each RCBO protects just one circuit, a fault on the kitchen sockets will not also switch off the lights or the fridge freezer. That is the main reason electricians now fit them. You can browse our full range of RCBOs for consumer units.
How does an RCBO work?

An RCBO has three ways of tripping, each aimed at a different fault.
1. Overload (thermal trip)
A bimetallic strip warms up when the current stays above the rating for too long, for example a heater, kettle and tumble dryer all on one circuit. The strip bends and trips the device before the cable overheats. The bigger the overload, the faster it trips.
2. Short circuit (magnetic trip)
If live touches neutral or earth, a huge current flows. A magnetic coil trips the RCBO almost instantly. The trip curve letter, such as B or C, tells you how big that current has to be.
3. Earth leakage (residual current trip)
The live and neutral both pass through a small current transformer. Normally the current going out equals the current coming back. If some leaks to earth, the imbalance is detected and the RCBO trips. A 30 mA device must disconnect within 300 ms at its rated leakage, and within 40 ms at five times that.
Pressing the T button creates a small deliberate imbalance to check the earth leakage mechanism works.
RCBO vs MCB vs RCD: what is the difference?

| Feature | MCB | RCD (RCCB) | RCBO |
|---|---|---|---|
| Overload protection | Yes | No | Yes |
| Short-circuit protection | Yes | No | Yes |
| Earth leakage / shock protection | No | Yes (usually 30 mA) | Yes (usually 30 mA) |
| Circuits covered | One | A group of circuits | One |
| If it trips | Only that circuit goes off | Every circuit on that RCD goes off | Only that circuit goes off |
| Test button | No | Yes | Yes |
| Product standard | BS EN 60898 | BS EN 61008 | BS EN 61009 |
RCBO vs MCB
An MCB only protects against overcurrent. It gives no protection against electric shock from earth leakage, so in a domestic board an MCB normally sits behind an RCD. An RCBO does both jobs for one circuit. It costs more per way than an MCB, but you no longer need a separate RCD for that circuit.
RCBO vs RCD (RCCB)
A stand-alone RCD, also called an RCCB, protects a group of circuits against earth leakage but has no overload or short-circuit protection of its own. In a split-load or dual-RCD board, one fault trips every circuit on that RCD. With RCBOs, only the faulty circuit goes off.
For a deeper look at every breaker type, including AFDDs and MCCBs, read our guide to the different types of circuit breakers.
What are the different RCBO types?
An RCBO label carries two kinds of "type", which often causes confusion. The trip curve (B, C or D) describes the overcurrent part. The RCD type (AC, A, F or B) describes which kinds of leakage current the residual current part can detect. A typical domestic RCBO is marked something like B32, 30 mA, Type A.
Trip curves: Type B and Type C RCBOs

| Trip curve | Instant (magnetic) trip at | Typical use |
|---|---|---|
| Type B | 3–5× rated current | Most domestic circuits: lighting, sockets, showers, cookers, immersion heaters |
| Type C | 5–10× rated current | Loads with a high start-up surge: motors, pumps, fans, large banks of LED lighting, commercial circuits |
| Type D | 10–20× rated current | Rare in RCBO form; heavy industrial loads such as large transformers and welders |
Type B suits almost every circuit in a home. Type C tolerates bigger start-up surges, but it needs a lower earth fault loop impedance to disconnect in time. Never swap a B for a C to cure nuisance tripping without an electrician checking the circuit. For a domestic example, see the Garo 6 A 30 mA single-module Type B RCBO.
RCD types: AC, A, F and B

| RCD type | Detects | Typical use | Status |
|---|---|---|---|
| Type AC | Sinusoidal AC leakage only | Simple resistive loads with no electronics | Restricted by BS 7671:2018 A2 to fixed equipment known to have no DC component |
| Type A | AC plus pulsating DC | General domestic circuits with modern electronics, LED drivers, chargers | The usual default today |
| Type F | As Type A, plus mixed-frequency leakage | Single-phase inverter-driven appliances: some washing machines, heat pumps, air conditioning | Specified where the equipment maker asks for it |
| Type B | As Type F, plus smooth DC | Some EV chargers, solar PV inverters, three-phase variable speed drives | Used where the manufacturer requires it |
Since Amendment 2 of BS 7671:2018, Type AC devices may only be used for fixed equipment where the load is known to contain no DC component. In practice that rules them out for general socket and lighting circuits, so Type A is the normal minimum for new work.
Pro tip: "Type B" on an RCBO can mean a B trip curve or a Type B RCD, which are completely different things. A B32 Type A RCBO is the usual domestic choice. A true Type B RCD (smooth DC detection) is a specialist and much more expensive device.
What does 30mA mean on an RCBO?
The 30 mA figure is the rated residual operating current: the leakage level at which the RCBO is designed to trip. Under BS 7671, 30 mA RCD protection is required as additional protection for socket outlets rated up to 32 A, for lighting circuits in homes, and for many cables buried in walls. 30 mA RCBOs cover all of these.
100 mA and 300 mA devices exist for fire protection or sub-main selectivity, but do not give the same shock protection.
Typical RCBO ratings in a UK home
The right rating always depends on the cable size, how it is installed and the load, but these are common examples:
| Circuit | Typical RCBO |
|---|---|
| Lighting | B6 (sometimes B10), 30 mA |
| Immersion heater | B16, 30 mA |
| Radial socket circuit (2.5 mm²) | B20, 30 mA |
| Ring final socket circuit (2.5 mm²) | B32, 30 mA |
| Cooker or oven | B32 to B40, depending on appliance and cable |
| Electric shower | B40 to B50, depending on shower kW and cable |
| 7 kW EV charger | B32, Type A or as the charger maker specifies |
Also check the breaking capacity, usually 6 kA or 10 kA for domestic RCBOs. It must suit the prospective fault current at the board.
Single-module vs 2-module RCBOs: which do you need?
RCBOs come in two common widths. Single-module RCBOs are the same width as an MCB.
| Single-module RCBO | 2-module RCBO | |
|---|---|---|
| Width | One module (about 18 mm), the same as an MCB | Two modules (about 36 mm) |
| Space in the board | Fits one RCBO per way, so a smaller board does more | Needs more ways, or a larger board |
| Neutral connection | Often a flying neutral lead to the neutral bar; some makes also need a functional earth lead | Usually a neutral terminal on the device |
| Poles switched | Many switch the line only; some are double pole | Usually double pole (line and neutral) |
Always use RCBOs from the same manufacturer and range as the consumer unit. Mixing brands can affect the fit, the busbar connection and the board's tested ratings. Our Garo range includes boards and matching RCBOs, and for three-phase work see our TP&N board RCBOs.
Why are RCBO consumer units so popular?

- Less disruption: a fault only trips one circuit, so you do not lose the lights, heating or freezer because a kettle is faulty.
- Fewer nuisance trips: small, normal leakage from many appliances adds up on a shared RCD. Spreading it across individual RCBOs reduces unwanted tripping, which BS 7671 asks designers to consider.
- Easier fault-finding: the device that trips tells you which circuit has the problem.
- Compact boards: single-module RCBOs mean an all-RCBO board can be similar in size to a dual-RCD board.
Are RCBOs mandatory in the UK?
No. BS 7671 requires 30 mA RCD protection on most domestic circuits, but it does not insist that it comes from RCBOs. A well-designed dual-RCD board with MCBs can still comply. RCBOs are simply the neatest way to meet the requirements while keeping each circuit independent.
Where are RCBOs used?

In homes they protect sockets, lighting, showers, cookers and EV chargers. In shops and offices they stop one fault taking down a whole floor. They also suit outdoor circuits such as garden lighting and external sockets, with the equipment in suitably IP-rated enclosures.
How do you choose and test an RCBO?

When choosing an RCBO, work through these checks in order:
- Match the board manufacturer and range.
- Set the rating to suit the cable and the load, for example B6 for lighting or B32 for a ring final circuit.
- Pick the trip curve: Type B for most domestic circuits, Type C only where the load needs it.
- Pick the RCD type: Type A as a minimum, or Type F or B where the equipment maker specifies it.
- Check the sensitivity and breaking capacity: 30 mA for additional protection, and at least the prospective fault current at the board.
- Check the module width and poles against the space in the board and any need for double-pole switching.
How often should you test an RCBO?
Press the test button regularly. The notice on your consumer unit recommends every six months. The RCBO should trip straight away; switch it back on afterwards. If it does not trip, have it checked and replaced. A full Electrical Installation Condition Report (EICR) by an electrician tests the actual trip times.
Credit: John Ward (jwflame).
Why does an RCBO keep tripping?
If it trips on overload or short circuit, too much is plugged in or there is a fault in a cable, accessory or appliance. If it trips on earth leakage, the cause is often a faulty appliance, a damp outdoor socket or damaged cable. Unplug everything, reset, then reconnect items one at a time. If it keeps tripping, stop resetting it and call an electrician.
Safety: Fitting or replacing RCBOs means working inside a consumer unit, where the incoming tails stay live even with the main switch off. The work must meet BS 7671 (I.S. 10101 in the Republic of Ireland) and may be notifiable. Use a qualified, registered electrician.
Key takeaways
- RCBO stands for residual current breaker with overcurrent protection: an MCB and an RCD in one device.
- It protects a single circuit against overload, short circuit and earth leakage, so a fault only trips that circuit.
- An MCB has no shock protection, and an RCD has no overcurrent protection. An RCBO has both.
- Check two "types": the trip curve (B for most homes) and the RCD type (Type A minimum; Type AC is now restricted).
- Most domestic RCBOs are 30 mA, single-module and Type A, and must match the consumer unit brand.
RCBO meaning in a nutshell
So, what is an RCBO? It is the device that gives every circuit its own overcurrent and earth leakage protection, which is why all-RCBO consumer units have become the go-to choice for new installations and upgrades. If you are planning a new board, our guide on how to install a consumer unit explains what is involved.
Shop RCBOs and consumer units
Single-module and 2-module RCBOs, MCBs, RCDs and boards from Garo and other leading brands. Trade prices, next working day delivery across NI & ROI on in-stock orders before 5pm.
Shop RCBOs Shop consumer unitsNeed help choosing? Call our team on 028 8675 1515 (048 from ROI), Monday to Friday, 8am–5pm.
FAQs
What does RCBO stand for?
RCBO stands for residual current breaker with overcurrent protection. It combines a miniature circuit breaker (MCB), which protects against overload and short circuit, with a residual current device (RCD), which protects against earth leakage and electric shock. One RCBO protects a single circuit, and it is made to BS EN 61009.
What is the difference between an RCBO and an MCB?
An MCB protects a circuit against overload and short circuit only, so it gives no protection against electric shock on its own. An RCBO does the same job and also detects earth leakage, usually at 30 mA. Because each RCBO covers one circuit, a fault only trips that circuit rather than a whole group.
Is an RCBO better than an RCD?
For most new boards, yes. An RCD protects a group of circuits against earth leakage only, so one fault switches several circuits off. An RCBO adds overcurrent protection and covers a single circuit, which means less disruption, fewer nuisance trips and easier fault-finding. A dual-RCD board can still comply with BS 7671.
What type of RCBO should I use in a house?
Most domestic circuits use a Type B trip curve, 30 mA, Type A RCBO, matched to the consumer unit brand. Type A detects AC and pulsating DC leakage from modern electronics. Type AC is now restricted by BS 7671, and some EV chargers, heat pumps or inverters may need Type F or Type B.
Can I replace an MCB with an RCBO?
Often yes, if the board maker offers a compatible RCBO for that range and there is room for it, and the neutral can be connected correctly. The rating and trip curve should match the circuit design. The work is inside a live consumer unit and must meet BS 7671, so use a registered electrician.
Why does my RCBO keep tripping?
An RCBO trips on overload, short circuit or earth leakage. Leakage trips are often caused by a faulty appliance, damp in an outdoor socket or damaged cable. Unplug everything on that circuit, reset it, then reconnect items one by one. If it still trips, have an electrician test the circuit and the device.
How often should I test an RCBO?
Press the test button on each RCBO every six months, as the notice on your consumer unit advises. It should trip immediately, and you then switch it back on. If it does not trip, the device needs checking and replacing. A periodic EICR by an electrician also measures the real trip times.